On 2016-03-31 the CPSC announced a recall of Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3) by Gamewell Fci, citing when configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.

Read the official CPSC notice

AgencyCPSC
Recall number16134
ClassificationNot classified
Statusunknown
Initiated2016-03-31
Published2016-03-31
Last updated2026-09-13 11:58 UTC
CompanyGamewell Fci
DistributionUS

Product

Gamewell-FCI fire alarm panels (ILI-MB-E3 and ILI-S-E3) | This recall is for the ILI-MB-E3 and ILI-S-E3 Gamewell-FCI fire alarm panels in commercial buildings. This issue is limited to a specific configuration of Signaling Line Circuit (SLC) devices. To occur, the SLC must include at least two of the following detectors in any combination: Acclimate, 4-Warn, Photo/CO and iFAAST. The issue would occur only if the detectors are addressed within the same FlashScan polling group. Detectors installed in a different combination are not affected.

Reason

When configured in a certain way, the panels can become non-responsive and connected detectors in the area can fail to detect and respond to an alarm.