CPSC recall 14711
Bosch GV4 Fire Alarm Control Panels
- CPSC
- unknown
- Published 2014-05-23
On 2014-05-23 the CPSC announced a recall of Bosch GV4 Fire Alarm Control Panels by Bosch Security Systems, citing the notification appliance circuit module can cause the panels to fail to activate an audible or visual alarm in the event of a fire.
| Agency | CPSC |
|---|---|
| Recall number | 14711 |
| Classification | Not classified |
| Status | unknown |
| Initiated | 2014-01-16 |
| Published | 2014-05-23 |
| Last updated | 2026-09-13 11:58 UTC |
| Company | Bosch Security Systems |
| Distribution | US |
Product
Bosch GV4 Fire Alarm Control Panels | The recall involves G-series Fire Alarm Control Panels that are professionally installed and have model numbers that end in GV4 and use D192G Notification Appliance Circuit (NAC) modules. The NAC module monitors the circuit connections and signals when alarms are not operational. The Bosch name, logo and model number D9412GV4, D7412GV4 or D7212GV4 are on the board of recalled GV4 fire alarm control panels. The control panels and modules are used in residences and commercial facilities and can be mounted inside a variety of enclosures with a minimum size of 16 inches x 16 inches x 3.5 inches, which may or may not be labeled with the Bosch name or logo.
Reason
The notification appliance circuit module can cause the panels to fail to activate an audible or visual alarm in the event of a fire.
Status history
No status changes recorded since RecallRadar first saw this recall on 2026-09-13 11:58 UTC. Current status: unknown.
Source
Official record: https://www.cpsc.gov/Recalls/2014/Bosch-Security-Systems-Recalls-Fire-Control-Panels
RecallRadar indexes public recall notices from the FDA, USDA FSIS, and CPSC. The official agency notice is the authoritative source. Always confirm details at the linked source before acting.