RecallRadar

CPSC recall 07565

Gamewell-FCI 600 Series SmartScan Fire Alarm Control Panels

On 2014-05-23 the CPSC announced a recall of Gamewell-FCI 600 Series SmartScan Fire Alarm Control Panels by Gamewell Fci, citing the software in the fire alarm system could fail to recognize when a detector needs servicing as a result of the buildup of dust, dirt, or other environmental pollutants, which co….

Read the official CPSC notice

AgencyCPSC
Recall number07565
ClassificationNot classified
Statusunknown
Initiated2007-07-27
Published2014-05-23
Last updated2026-09-13 11:58 UTC
CompanyGamewell Fci
DistributionUS

Product

Gamewell-FCI 600 Series SmartScan Fire Alarm Control Panels | The software upgrade involves the Gamewell-FCI model 600 Series control panel using System Sensor compatible line cards, SmartScan. These panels are components of the Gamewell-FCI 600 Series fire alarm system. They provide the signaling line circuits and display information for the system.

Reason

The software in the fire alarm system could fail to recognize when a detector needs servicing as a result of the buildup of dust, dirt, or other environmental pollutants, which could result in the system failing to respond in the event of a fire.

Status history

No status changes recorded since RecallRadar first saw this recall on 2026-09-13 11:58 UTC. Current status: unknown.

Source

Official record: https://www.cpsc.gov/Recalls/2007/Gamewell-FCI-Recalls-to-Upgrade-Software-Used-with-Fire-Alarm-System-Control-Panels

RecallRadar indexes public recall notices from the FDA, USDA FSIS, and CPSC. The official agency notice is the authoritative source. Always confirm details at the linked source before acting.