Greenheck Sidewall, Rooftop and Centrifugal Inline Ventilation Units
- CPSC
- unknown
- Published 2025-01-02
On 2025-01-02 the CPSC announced a recall of Greenheck Sidewall, Rooftop and Centrifugal Inline Ventilation Units by Greenheck Fan, citing LUX 3/8-inch spinlock bolts supplied with these units may not have been properly heat treated, which can result in the bolts breaking. Bolt failure during lifting for rooftop inst….
| Agency | CPSC |
|---|---|
| Recall number | 05605 |
| Classification | Not classified |
| Status | unknown |
| Initiated | 2005-09-30 |
| Published | 2025-01-02 |
| Last updated | 2026-09-13 11:58 UTC |
| Company | Greenheck Fan |
| Distribution | US |
Product
Greenheck Sidewall, Rooftop and Centrifugal Inline Ventilation Units | Affected units are Sidewall, Rooftop and Centrifugal Inline ventilation units built between August 11, 2004 and April 29, 2005, containing 16-thread-per-inch 3/8-inch by ¾-inch spinlock bolts with LUX head markings. Affected model numbers are RBU, RBUMO, RDU, RB/R, SB/S, and BSU 360-420 with serial numbers 04HXXXXX through 05DXXXXX. The model and serial numbers are found on metal identification plate on the units.
Reason
LUX 3/8-inch spinlock bolts supplied with these units may not have been properly heat treated, which can result in the bolts breaking. Bolt failure during lifting for rooftop installation or after installation could cause the unit or components to fall and injure bystanders.